Skip to content Skip to navigation menu
click to open Expanded view

Terasaki - Tb2 MCCB 70Ka 3P 125A Electronic - S250PE3125

  • TERASAKI
  • BW#: 00813896
  • Mfr#: S250PE3125
  • UNSPSC#: 39121616
Login or Register to view price
QTY



Specifications

 • Service Information: Product is not repairable
 • Product Series: TemBreak 2 MCCB
 • Standards Compliance: IEC 60947-2, AS/NZS 60947-2, EN 60947-2, JIS C 8201-2-1 Ann.1, NEMA AB1
 • Certifications: CE
 • Component Type MCCB: MCCB AC
 • Standard Installation Method: Front Connection
 • Trip Unit Protection Type: Electronic
 • In, Rated Current at 45°C: 125 A @45°C
 • Ir, Thermal Trip Current, Max: 125 A
 • Ir, Thermal Trip Current, Min: 50 A
 • Icu, Rated Ultimate Short-Circuit Breaking Capacity, 220/240V AC: 125 kA @220/240VAC
 • Icu, Rated Ultimate Short-Circuit Breaking Capacity, 400/415V AC: 70 kA @400/415VAC
 • Icu, Rated Ultimate Short-Circuit Breaking Capacity, 440V AC: 50 kA @440VAC
 • Icu, Rated Ultimate Short-Circuit Breaking Capacity, 525V AC: 35 kA @525VAC
 • Icu, Rated Ultimate Short-Circuit Breaking Capacity, 690V AC: 20 kA @690VAC
 • Depth: 103 mm
 • Frame Size: 250 AF size
 • Height: 165 mm
 • Number of Poles: 3
 • Electrical Service Life at Un, In: 10000 cycles
 • Mechanical Service Life: 30000 cycles
 • Thermal Trip Type: Adjustable type
 • Ui, Rated Insulation Voltage: 800 V (rms)
 • Un, Nominal Operational Voltage, AC: 690 V AC
 • Weight: 2.5 kg
 • Width: 105 mm
 • Reverse Connection Of Supply Possible: Yes

Minimum sell quantity:

Order Quantity Multiple:

Technical Specifications

Type MCCB AC
Number of Pole 3
Height 165 mm
Width 105 mm
Weight 2.5 kg
Rated Current 125 A @45°C
Rated Insulation Voltage 800 V (rms)
Trip Unit Technology Electronic