Skip to content Skip to navigation menu
click to open Expanded view

Terasaki - Tb2 MCCB 1000V AC 18Ka 3P 250A Electronic - VS400NE3250

  • TERASAKI
  • BW#: 00809391
  • Mfr#: VS400NE3250
  • UNSPSC#: 39121616
Login or Register to view price
QTY

Features
  • 1000 VAC MCCB for power distribution and motor starting use in mines or tunnels


  • Specifications

  • Standards Compliance: IEC 60947-1, IEC 60947-2, JIS C 8201-2-1 Ann.1
  • Certifications: CE, RCM
  • Shipping Approvals: Contact NHP
  • Component Type MCCB: MCCB AC
  • Trip Unit Protection Type: Electronic LSI
  • Altitude, Operating (No Derating): 2000 m
  • Connection Mode: Cable Tunnel Clamp (Option), Extension Bar (Option), Front Connection, Rear Connection (Option)
  • Terminal Type: Bolt-Terminal
  • In, Nominal Current: 250 A
  • In, Rated Current at 30°C: 250 A @30°C
  • In, Rated Current at 40°C: 250 A @40°C
  • In, Rated Current at 45°C: 250 A @45°C
  • Ics, Rated Service Short-Circuit Breaking Capacity, 1000V AC: 13.5 kA
  • Ir, Thermal Trip Current, Max: 250 A
  • Ir, Thermal Trip Current, Min: 100 A
  • Icu, Rated Ultimate Short-Circuit Breaking Capacity, 1000V AC: 18 kA @1kVAC
  • Icu, Rated Ultimate Short-Circuit Breaking Capacity, 1100V AC: 12.5 kA @1.1kVAC
  • Dielectric Strength: 3500 V AC
  • Frame Size: 400 AF size
  • Rated Frequency: 50/60 Hz
  • Height: 260 mm
  • Relative Humidity, Max: 85 %RH
  • Number of Poles: 3
  • Poles: 3P
  • Switching Poles: 3P
  • Pollution Degree: 3
  • Operating Temperature, Max: 70 °C max
  • Operating Temperature, Min: -5 °C min
  • Storage Temperature, Max: 70 °C max
  • Storage Temperature, Min: -10 °C min
  • Tightening Torque, Max: 22.5 Nm
  • Tightening Torque, Min: 13.7 Nm
  • Thermal Trip Type: Fixed type
  • Utilisation Category: A
  • Vibration Acceleration (Max.): 19 m/s²
  • Vibration Duration (Max.): 12 min
  • Vibration Frequency, Operational (Max.): 16.7 Hz
  • Uimp, Impulse Withstand Voltage: 8 kV
  • Ui, Rated Insulation Voltage: 1100 V (rms)
  • Ui, Rated Insulation Voltage, AC: 1100 V AC
  • Ue, Rated Operational Voltage, AC, max: 1100 V AC
  • Weight: 5 kg
  • Width: 140 mm
  • Cable Cross Section (Max): 185 mm²
  • Cable Cross Section (Min): 35 mm²
  • Supply Voltage Type: AC
  • Electrical Life: 1000 cycles
  • Withdrawable: No. AC Power loss per pole at full rated current: 16.6 W
  • Depth (less toggle): 103 mm
  • Depth (toggle included): 145 mm
  • DIN rail mounting with optional adapter: No. General Accessories: Alarm Switch, Auxiliary Switches, External Panel Display, Handle Operators, Interpole Barriers, Locking Devices, Mechanical Interlock, Motor Operator, Shunt Trip, Terminal Covers, Under Voltage Trip
  • Ics, Rated Service Short-Circuit Breaking Capacity, 1100V AC: 15 kA
  • In, Rated Current at 35°C: 250 A @35°C
  • In, Rated Current at 50°C: 250 A @50°C
  • In, Rated Current at 55°C: 237 A @55°C
  • In, Rated Current at 60°C: 230 A @60°C
  • In, Rated Current at 65°C: 223 A @65°C
  • In, Rated Current at 70°C: 200 A @70°C
  • Mechanical Life: 7000 cycles
  • Model: VS
  • Rated temperature of trip unit: 50 °C
  • Suitable for Mounting on Chassis: No. Suitable for Panel Mounting: Yes
  • Trip Unit Rating: 250 A
  • Type of Power Supply: AC AC/DC
  • Minimum sell quantity:

    Order Quantity Multiple:

    Technical Specifications

    Type MCCB AC
    Number of Pole 3
    Terminal Type Bolt-Terminal
    Mounting Type Suitable for Panel Mounting
    Height 260 mm
    Width 140 mm
    Weight 5 kg
    Rated Current 250 A @45°C
    Rated Insulation Voltage 1100 V (rms)
    Electrical Durability 1000 cycles
    Trip Unit Technology Electronic LSI
    Mechanical Durability 7000 cycles
    Customers Also Bought