Skip to content Skip to navigation menu
click to open Expanded view
Phoenix Contact Phoenix Contact (View All Products)

Phoenix Contact 2866789 - Primary-Switched Quint Power Supply - For Din Rail Mounting - Input: 1-Phase - Output: 24 V DC - 40 A

  • Phoenix Contact
  • BW#: 01111600
  • Mfr#: 2866789
  • UNSPSC#: 39101600
Login or Register to view price
QTY

Features
  • QUINT POWER power supplies with maximum functionality
  • QUINT POWER circuit breakers magnetically and therefore quickly trip at six times the nominal current, for selective and therefore cost-effectivesystem protection
  • The high level of system availability is additionally ensured, thanks to preventive function monitoring, as it reports criticaloperating states before errors occur
  • Reliable starting of heavy loads takes place via the static power reserve POWER BOOST
  • Thanks to the adjustable voltage, all ranges between 5V DC ... 56 V DC are covered
  • Your advantages For superior system availability
  • Fast tripping of standard circuit breakers with dynamic power reserve SFB (selective fuse breaking) technology with up to 6 times the nominal current for 12 ms
  • Reliable starting of difficult loads with the static POWER BOOST power reserve with up to 1.5 times the nominal current permanently
  • Preventive function monitoring


  • Specifications

  • Ambient conditions
  • Degree of protection IP20
  • Ambient temperature (operation) -25 °C ... 70 °C (> 60 °C
  • Derating: 2.5 %/K)
  • Ambient temperature (start-up type tested) -40 °C
  • Ambient temperature (storage/transport) -40 °C ... 85 °C
  • Max. permissible relative humidity (operation) ≤ 95 % (at 25 °C, non-condensing)
  • Climatic class 3K3 (in acc. with EN 60721)
  • Degree of pollution 2
  • Installation height 4000 m
  • Input data
  • Nominal input voltage range 100 V AC ... 240 V AC120 V DC ... 300 V DC (UL 508: ≤ 250 V DC)
  • Input voltage range 85 V AC ... 264 V AC90 V DC ... 300 V DC (UL 508: ≤ 250 V DC)
  • Dielectric strength maximum 300 V ACAC frequency range 45 Hz ... 65 Hz
  • Frequency range DC 0 Hz
  • Discharge current to PE < 3.5 mA
  • Current consumption 8.8 A (120 V AC)4.6 A (230 V AC)9.5 A (110 V DC)4.7 A (220 V DC)
  • Nominal power consumption 1157 VA
  • Inrush current < 15 A (typical)
  • Mains buffering time > 35 ms (120 V AC)> 35 ms (230 V AC)
  • Input fuse 20 A (slow-blow, internal)
  • Recommended breaker for input protection 16 A ... 20 A (AC: Characteristics B, C, D, K)
  • Power factor (cos phi) 0.88
  • Type of protection Transient surge protection
  • Protective circuit/component Varistor, gas-filled surge arrester
  • Output data
  • Nominal output voltage 24 V DC ±1 %Setting range of the output voltage (USet) 18 V DC ... 29.5 V DC (> 24 V DC, constant capacity restricted)
  • Nominal output current (IN) 40 A (-25 °C ... 60 °C, UOUT = 24 V DC)
  • Minimum sell quantity:

    Order Quantity Multiple:

    Technical Specifications

    Alternate Products