Skip to content Skip to navigation menu
click to open Expanded view

IME DSRM110VC ELR Mining Kit - Panel Mount Relay & Test Unit - 110V - AC 0.03-5A - 120 x 150 x 100 mm

  • IME
  • BW#: 00354182
  • Mfr#: DSRM110VC
  • UNSPSC#: 41113640
Login or Register to view price
QTY

Features
  • 1 x trip change-over latching contact

  • Second change-over latching contact selectable trip or power fail

  • LED indication 20%, 30, 40% and 50%

  • Field selectable positive or negative security

  • 30mA - 5A sensitivity and up to 5s time delay

  • Harmonic filter

  • Panel mount relay - 1 relay (72 x 72mm) and 1 test unit (48 x 48mm)


Applications
  • Mining

  • Industrial

  • Commercial


Specifications

  • Product Series: DSRM
  • Standards Compliance: AS/NZS 2081.3, EN 60439-1, EN 61010-1, EN 50081-1, EN 55011, EN 50082-2, IEC 60755
  • Visible Trip Indicator: Red LED
  • Component Type Power Distribution & Protection: Earth Leakage Relay
  • Burden, Rated: 2.5 VA
  • Installation Category: III
  • Contact Configuration: 2 CO
  • Configuration Method: Potentiometer/DIP-Switch
  • Terminal Type: Fast-On Crimp Terminal(s)
  • Details, Alarm: TRIP state memorisation: red LED “TRIP" + relay latching
  • Details, compatible Product Series: DSRM72C110 & DSRTD48C110
  • Details, Function: Local pushbutton or remote closing contact details
  • Details, Output(s): 1 SPDT latching alarm contact and 1 SPDT latching contact selectable alarm or power fail alarm
  • Input Frequency, Nom: 50 Hz
  • Operational Frequency, Max: 63 Hz max
  • Operational Frequency, Min: 47 Hz min
  • Height, Cutout: 68 mm
  • Relative Humidity, Average: 50 %RH
  • Humidity Type: Suitable for tropical enviroments
  • IP Rating, Front: IP40
  • IP Rating, Terminals: IP20
  • Material, Body/Housing: Plastic
  • PC (Polycarbonate) self-extinguishing material
  • Mounting: Panel Mount
  • Number of Alarm Contacts: 2
  • Number of Setpoints: 14
  • Pollution Degree: 2
  • Power Dissipation, Max: 3.5 W
  • Setpoint Range(s): 0.03 - 5A, Configurable
  • Operating Temperature, Max: 60 °C max
  • Operating Temperature, Min: -5 °C min
  • Storage Temperature, Max: 70 °C max
  • Storage Temperature, Min: -40 °C min
  • Uimp, Impulse Withstand Voltage: 5 kV
  • Ui, Rated Insulation Voltage: 450 V (rms)
  • Umax, Supply Voltage, AC, Max: 127 V AC
  • Umin, Supply Voltage, AC, Min: 97 V AC
  • Unom, Supply Voltage, AC, Nom: 110 V AC
  • Nominal Supply Voltage, AC, Max: 127 V AC max
  • Nominal Supply Voltage, AC, Min: 97 V AC min
  • Weight: 0.28 kg
  • Width, Cutout: 68 mm
  • Reset Type: Manual local or Remote
  • Details, Connection: Low voltage lines, with TD series, 4 wire
  • Details, Indicator: Power on: green LED “ON"
  • Transformer connection failure: red LED “TRIP" and relay “TRIP" switching
  • Ring current transformer-relay connection failure: red LED “TRIP" blinking + “TRIP" relay switching
  • Trip Time, Max: 500 ms
  • Trip Time, Min: 50 ms
  • Alarm Function: Yes
  • Reverse Polarity Protection: No Y/N
  • Current set point IΔn: 0.03, 0.06, 0.1, 0.2, 0.3, 0.4, 0.5, 2 ranges x1, x10
  • Display Technology: LED Sequence
  • Frequency Tolerance: 47-63 Hz
  • Insulation Class: III
  • Intervention time t:: 0.05, 0.1, 0.15, 0.2, 0.3, 0.4, and 0.5 s
  • IΔn, Leakage Current, Max: 5 A
  • Non-operating residual current (IEC60755): 50% IΔn
  • Power On: Green LED
  • RCD Type, AS/NZS 60947-2: A
  • Waveform: Sinusoidal (type AC) or chopped pulsating with superimposed D.C. (type A) according to EN60947-2 (annex Band M) IEC60947-2
  • Minimum sell quantity:

    Order Quantity Multiple:

    Technical Specifications

    Type Earth Leakage Relay
    Display LED Sequence
    Frequency 63 Hz max, 47 Hz min
    Width/Depth Cutout : 68 mm
    Feature Humidity Type : Suitable for tropical enviroments
    Height Cutout : 68 mm
    Size 120x150x100mm
    Colour Yellow
    Alternate Products