Skip to content Skip to navigation menu
click to open Expanded view
Schneider Electric Schneider Electric (View All Products)

Schneider Electric TeSys Deca LC1D38B7 Contactor - 3P - 3NO - AC3 - 440V - 38A - 24V AC - 50/60Hz Coil

  • Schneider Electric
  • BW#: 08633372
  • Mfr#: LC1D38B7
  • UNSPSC#: 39122118

Features
  • AC & DC Coils 50/60 Hz available for whole range
  • DC low consumption with direct compatibility with 100 mA I/O PLC card from 9 to 38 A
  • DC low consumption with direct compatibility with 500 mA I/O PLC card from 40 to 80 A using TeSys D Green BBE 24 V electronic coil
  • Various types of connection available: Screw clamp terminals, everlink (40 to 80 A), Spring terminals (9 to 38 A and on control terminal up to 65 A), Lugs terminals, Faston terminal (9 to 12 A)
  • High making and breaking capacity
  • 1 NO & 1 NC integrated auxiliary contact in all 3-pole and 4-pole contactors
  • Up to 30 million mechanical operation cycles
  • Electrical cycles up to 3600 cycles per hour at ambient temperature
  • No derating up to 3000 m altitude
  • Working temperature: -25°C to 60°C
  • 4 width sizes available to cover all ratings
  • 45 mm to 38 A
  • 55 mm from 40 to 65 A
  • 85 mm from 80 to 95 A
  • 120 mm from 115 to 150 A


  • Applications
  • TeSys D contactors have been designed for perfect integration in control systems, specific references BL or BBE compatible with digital PLC I/O 100 mA or 500 mA
  • These contactors can be used to create motor starters for any type of application


  • Specifications

     • UL 508 Listed
     • CSA C22.2 No.14 Certified
     • EN 60947-4-1, EN 60947-5-1, IEC 60947-4-1, IEC 60947-5-1
     • RoHS Compliant, REACh Compliant
     • Product Certifications : CSA
     • Lros (Lloyds Register Of Shipping)
     • Bv
     • Rina
     • Ul
     • Gost
     • Dnv
     • CCC
     • Gl
     • Non-Overlap Time : 1.5 Ms On De-Energisation Between Nc And No Contact
     • 1.5 Ms On Energisation Between Nc And No Contact
     • Minimum Switching Current : 5 Ma For Signalling Circuit
     • [Uc] Control Circuit Voltage : 24 V AC 50/60 Hz
     • [Ue] Rated Operational Voltage : Power Circuit: <= 690 V AC 25...400 Hz
     • Power Circuit: <= 300 V DC
     • Power Dissipation Per Pole : 5 W Ac-1
     • 3 W Ac-3
     • 3 W Ac-3E
     • Average Impedance : 2 Mohm - Ith 50 A 50 Hz For Power Circuit
     • Auxiliary Contact Composition : 1 No + 1 Nc
     • Mounting Support : Rail
     • Plate
     • Contact Compatibility : M2
     • Contactor Application : Resistive Load
     • Motor Control
     • Insulation Resistance : > 10 Mohm For Signalling Circuit
     • Product Name : Tesys D
     • Tesys Deca
     • Power Range : 7-11 Kw At 200-240 V 3 Phases
     • 15-25 Kw At 380-440 V 3 Phases
     • 15-25 Kw At 480-500 V 3 Phases
     • 15-25 Kw At 525-690 V 3 Phases
     • 4-6 Kw At 100-120 V 3 Phases
     • Net Weight : 0.38 Kg
     • Inrush Power In Va : 70-70 Va 60 Hz Cos Phi 0.75 (At 20 °C)
     • 70-70 Va 50 Hz Cos Phi 0.75 (At 20 °C)
     • [Uimp] Rated Impulse Withstand Voltage : 6 Kv Conforming To IEC 60947
     • Pole Contact Composition : 3 No
     • Coil Technology : Without Built-In Suppressor Module
     • Utilisation Category : Ac-4
     • Ac-1
     • Ac-3
     • Ac-3E
     • [Ie] Rated Operational Current : 50 A (At <60 °C) At <= 440 V AC Ac-1 For Power Circuit
     • 38 A (At <60 °C) At <= 440 V AC Ac-3 For Power Circuit
     • 38 A (At <60 °C) At <= 440 V AC Ac-3E For Power Circuit
     • Flame Retardance : V1 Conforming To Ul 94
     • Maximum Operating Rate : 3600 Cyc/H 60 °C
     • Auxiliary Contacts Type : Type Mechanically Linked 1 No + 1 Nc Conforming To IEC 60947-5-1
     • Type Mirror Contact 1 Nc Conforming To IEC 60947-4-1
     • Poles Description : 3P
     • Operating Altitude : 0...3000 M
     • Hold-In Power Consumption In VA : 7.5-7.5 Va 60 Hz Cos Phi 0.3 (At 20 °C)
     • 7-7 Va 50 Hz Cos Phi 0.3 (At 20 °C)
     • Operating Time : 4...19 Ms Opening
     • 12...22 Ms Closing
     • Width : 45 mm
     • Overvoltage Category : Iii
     • Depth : 92 mm
     • Motor Power Kw : 18.5 Kw At 500 V AC 50/60 Hz (AC-3)
     • 18.5 Kw At 660...690 V AC 50/60 Hz (AC-3)
     • 7.5 Kw At 400 V AC 50/60 Hz (AC-4)
     • 18.5 Kw At 380...400 V AC 50/60 Hz (AC-3)
     • 9 Kw At 220...230 V AC 50/60 Hz (AC-3)
     • 18.5 Kw At 415...440 V AC 50/60 Hz (AC-3)
     • 18.5 Kw At 500 V AC 50/60 Hz (AC-3E)
     • 18.5 Kw At 660...690 V AC 50/60 Hz (AC-3E)
     • 18.5 Kw At 380...400 V AC 50/60 Hz (AC-3E)
     • 9 Kw At 220...230 V AC 50/60 Hz (AC-3E)
     • 18.5 Kw At 415...440 V AC 50/60 Hz (AC-3E)
     • Motor Power Hp : 10 Hp At 230/240 V AC 50/60 Hz For 3 Phases Motors
     • 10 Hp At 200/208 V AC 50/60 Hz For 3 Phases Motors
     • 5 Hp At 240 V AC 50/60 Hz For 1 Phase Motors
     • 20 Hp At 480 V AC 50/60 Hz For 3 Phases Motors
     • 25 Hp At 600 V AC 50/60 Hz For 3 Phases Motors
     • [Ui] Rated Insulation Voltage : Power Circuit: 600 V CSA Certified
     • Power Circuit: 600 V Ul Certified
     • Signalling Circuit: 690 V Conforming To IEC 60947-1
     • Signalling Circuit: 600 V CSA Certified
     • Signalling Circuit: 600 V Ul Certified
     • Power Circuit: 690 V Conforming To IEC 60947-4-1
     • Protective Cover : With
     • Mechanical Robustness : Vibrations Contactor Open: 2 Gn, 5...300 Hz
     • Vibrations Contactor Closed: 4 Gn, 5...300 Hz
     • Shocks Contactor Closed: 15 Gn For 11 Ms
     • Shocks Contactor Open: 8 Gn For 11 Ms
     • Ambient Air Temperature For Operation : -40-60 °C
     • 60-70 °C With Derating
     • Height : 85 mm
     • Range Of Product : Tesys D
     • Tesys Deca
     • [Ith] Conventional Free Air Thermal Current : 10 A (At 60 °C) For Signalling Circuit
     • 50 A (At 60 °C) For Power Circuit
     • Control Circuit Voltage Limits : 0.3...0.6 Uc (-40-70 °C):Drop-Out Ac 50/60 Hz
     • 0.8...1.1 Uc (-40-60 °C):Operational Ac 50 Hz
     • 0.85...1.1 Uc (-40-60 °C):Operational Ac 60 Hz
     • 1...1.1 Uc (60-70 °C):Operational Ac 50/60 Hz
     • Control Circuit Type : Ac At 50/60 Hz
     • Standards :
     • IEC 60335-1
     • Safety Reliability Level : B10D = 1369863 Cycles Contactor With Nominal Load Conforming To EN/ISO 13849-1
     • B10D = 20000000 Cycles Contactor With Mechanical Load Conforming To EN/ISO 13849-1
     • Pollution Degree : 3
     • Rated Breaking Capacity : 550 A At 440 V For Power Circuit Conforming To IEC 60947
     • Irms Rated Making Capacity : 140 A Ac For Signalling Circuit Conforming To IEC 60947-5-1
     • 250 A Dc For Signalling Circuit Conforming To IEC 60947-5-1
     • 550 A At 440 V For Power Circuit Conforming To IEC 60947
     • Associated Fuse Rating : 10 A Gg For Signalling Circuit Conforming To IEC 60947-5-1
     • 63 A Gg At <= 690 V Coordination Type 1 For Power Circuit
     • 63 A Gg At <= 690 V Coordination Type 2 For Power Circuit
     • Connections - Terminals : Control Circuit: Screw Clamp Terminals 2 Cable(S) 1-2.5 mm²Flexible With Cable End
     • Control Circuit: Screw Clamp Terminals 1 Cable(S) 1-4 mm²Flexible Without Cable End
     • Control Circuit: Screw Clamp Terminals 2 Cable(S) 1-4 mm²Flexible Without Cable End
     • Control Circuit: Screw Clamp Terminals 1 Cable(S) 1-4 mm²Flexible With Cable End
     • Control Circuit: Screw Clamp Terminals 1 Cable(S) 1-4 mm²Solid Without Cable End
     • Control Circuit: Screw Clamp Terminals 2 Cable(S) 1-4 mm²Solid Without Cable End
     • Power Circuit: Screw Clamp Terminals 1 Cable(S) 2.5-10 mm²Flexible Without Cable End
     • Power Circuit: Screw Clamp Terminals 2 Cable(S) 2.5-10 mm²Flexible Without Cable End
     • Power Circuit: Screw Clamp Terminals 1 Cable(S) 1-10 mm²Flexible With Cable End
     • Power Circuit: Screw Clamp Terminals 2 Cable(S) 1.5-6 mm²Flexible With Cable End
     • Power Circuit: Screw Clamp Terminals 1 Cable(S) 1.5-10 mm²Solid Without Cable End
     • Power Circuit: Screw Clamp Terminals 2 Cable(S) 2.5-10 mm²Solid Without Cable End
     • Range : Tesys
     • Tesys Deca
     • Device Short Name : Lc1D38
     • Lc1D
     • Motor Starter Type : Direct On-Line Contactor
     • Minimum Switching Voltage : 17 V For Signalling Circuit
     • Ambient Air Temperature For Storage : -60-80 °C
     • Signalling Circuit Frequency : 25...400 Hz
     • Tightening Torque : Control Circuit: 1.7 N.M - On Screw Clamp Terminals - With Screwdriver Flat Ø 6 mm
     • Control Circuit: 1.7 N.M - On Screw Clamp Terminals - With Screwdriver Philips No 2
     • Power Circuit: 2.5 N.M - On Screw Clamp Terminals - With Screwdriver Flat Ø 6 mm
     • Power Circuit: 2.5 N.M - On Screw Clamp Terminals - With Screwdriver Philips No 2
     • Control Circuit: 1.7 N.M - On Screw Clamp Terminals - With Screwdriver Pozidriv No 2
     • Power Circuit: 2.5 N.M - On Screw Clamp Terminals - With Screwdriver Pozidriv No 2
     • Protective Treatment : Th Conforming To IEC 60068-2-30
     • Electrical Durability : 1.4 Mcycles 50 A Ac-1 At Ue <= 440 V
     • 1.4 Mcycles 38 A Ac-3 At Ue <= 440 V
     • 1.4 Mcycles 38 A Ac-3E At Ue <= 440 V
     • Mechanical Durability : 15 Mcycles
     • Compatibility Code : Lc1D
     • IP Degree Of Protection : IP20 Front FaCE Conforming To IEC 60529
     • Fire Resistance : 850 °C Conforming To IEC 60695-2-1
     • [Icw] Rated Short-Time Withstand Current : 60 A 40 °C - 10 Min For Power Circuit
     • 430 A 40 °C - 1 S For Power Circuit
     • 150 A 40 °C - 1 Min For Power Circuit
     • 310 A 40 °C - 10 S For Power Circuit
     • 100 A - 1 S For Signalling Circuit
     • 120 A - 500 Ms For Signalling Circuit
     • 140 A - 100 Ms For Signalling Circuit
     • Heat Dissipation : 2-3 W At 50/60 Hz

    Minimum sell quantity:

    Order Quantity Multiple:

    Catalogue Page Number: 17-75

    Technical Specifications

    Type Contactor