Skip to content Skip to navigation menu
click to open Expanded view
Schneider Electric Schneider Electric (View All Products)

Schneider Electric Harmony RE22R2MYMR Modular Timing Relay - Multifunction - 0.05 S-300 H - 8A - 2 CO - 24 -240V AC/DC

  • Schneider Electric
  • BW#: 02662833
  • Mfr#: RE22R2MYMR
  • UNSPSC#: 39121523

Features
  • Wide power supply range from 24 to 240 V
  • Single or multiple functions
  • Single or multi timing ranges from 0.02s to 999 hrs
  • Screw or spring connection terminals
  • Relay or Solid-state output
  • Diagnostic button and dial pointer LED indicator
  • Module DIN rail mount, miniature plug-in and panel mount


  • Applications
  • Machines: single machine, and industrial automation and processes
  • Buildings: lighting control, access control door looks, roller shutters
  • Water segment: pumping and irrigation systems
  • HVAC: fans and centralized water system


  • Specifications

     • Compliant with international standards and certifications IEC 61812-1, EN 61812-1 UL, CSA, GL, RCM, EAC, CCC, China ROHS
     • Product Certifications :
     • Ce
     • Ul
     • Gl
     • Power Consumption In W : 1.5 W At 240 V DC
     • Connections - Terminals : Screw Connectors
     • Screw Terminals, 1 X 0.5...1 X 3.3 mm² (Awg 20...Awg 12) Solid Without Cable End
     • Screw Terminals, 2 X 0.5...2 X 2.5 mm² (Awg 20...Awg 14) Solid Without Cable End
     • Screw Terminals, 1 X 0.2...1 X 2.5 mm² (Awg 24...Awg 14) Flexible With Cable End
     • Screw Terminals, 2 X 0.2...2 X 1.5 mm² (Awg 24...Awg 16) Flexible With Cable End
     • Creepage Distance : 4 Kv/3 Conforming To IEC 60664-1
     • Standards : Ul 508
     • Switching Capacity In Va : 2000 Va
     • Dielectric Strength : 2.5 Kv For 1 Ma/1 Minute At 50 Hz Between Relay Output And Power Supply With Basic Insulation Conforming To IEC 61812-1
     • Shock Resistance : 15 Gn Not Operating For 11 Ms Conforming To IEC 60068-2-27
     • 5 Gn In Operation For 11 Ms Conforming To IEC 60068-2-27
     • Product Or Component Type : Multifunction Relay
     • Vibration Resistance : 20 M/S² (F= 10-150 Hz) Conforming To IEC 60068-2-6
     • Mounting Position : Any Position
     • Voltage Drift : +/- 0.2 %/V
     • Reset Time : 120 Ms On De-Energisation
     • Time Delay Range : 3...30 Min
     • 30...300 Min
     • 0.3...3 S
     • 3...30 H
     • 10...100 S
     • 1...10 S
     • 0.05...1 S
     • 30...300 S
     • 30...300 H
     • 3...30 S
     • Overvoltage Category : Iii Conforming To IEC 60664-1
     • Input Voltage : <= 2.4 V
     • Mounting Support : 35 mm Din Rail Conforming To EN/IEC60715
     • Nominal Output Current : 8 A
     • Housing Material : Self-Extinguishing
     • [In] Rated Current : 5 A
     • Status Led : Led Backlight Green (Steady) For Dial Pointer Indication
     • Led Yellow (Steady) For Output Relay Energised
     • Led Yellow (Fast Flashing) For Timing In Progress And Output Relay De-Energised
     • Led Yellow (Slow Flashing) For Timing In Progress And Output Relay Energised
     • Output Type : Relay
     • Time Delay Type : A, At, Aw, C, Ct, D, Di, Dit, Diw, Dt, Dw, H, Ht, Hw, Qg,Qgt,Qgw,Qt,Qtt,Qtw,W,Wt
     • Power On-Delay
     • Off-Delay
     • Symmetrical Flashing
     • Interval
     • Star-Delta
     • Supply Frequency : 50...60 Hz +/- 5 %
     • Repeat Accuracy : +/- 0.5 % Conforming To IEC 61812-1
     • Safety Reliability Data : B10D = 160000
     • Mttfd = 171.2 Years
     • Discrete Output Type : Relay
     • Ambient Air Temperature For Operation : -20-60 °C
     • Setting Accuracy Of Time Delay : +/- 10 % Of Full Scale At 25 °C Conforming To IEC 61812-1
     • Maximum Delay Response : 100 Ms
     • Control Type : Rotary Knob
     • Diagnostic Button
     • Potentiometer External
     • Range Of Product : Harmony Timer Relays
     • Insulation Resistance : 100 Mohm At 500 V DC Conforming To IEC 60664-1
     • Immunity To Microbreaks : 10 Ms
     • Power Consumption In VA : 3-3 Va At 240 V AC
     • Electromagnetic Compatibility : Fast Transients Immunity Test - Test Level: 1 Kv Level 3 (Capacitive Connecting Clip) Conforming To IEC 61000-4-4
     • Surge Immunity Test - Test Level: 1 Kv Level 3 (Differential Mode) Conforming To IEC 61000-4-5
     • Surge Immunity Test - Test Level: 2 Kv Level 3 (Common Mode) Conforming To IEC 61000-4-5
     • Electrostatic Discharge - Test Level: 6 Kv Level 3 (Contact Discharge) Conforming To IEC 61000-4-2
     • Electrostatic Discharge - Test Level: 8 Kv Level 3 (Air Discharge) Conforming To IEC 61000-4-2
     • Radiated Radio-Frequency Electromagnetic Field Immunity Test - Test Level: 10 V/M Level 3 (80 Mhz...1 Ghz) Conforming To IEC 61000-4-3
     • Conducted Rf Disturbances - Test Level: 10 V Level 3 (0.15...80 Mhz) Conforming To IEC 61000-4-6
     • Fast Transient Bursts - Test Level: 2 Kv Level 3 (Direct Contact) Conforming To IEC 61000-4-4
     • Immunity To Microbreaks And Voltage Drops - Test Level: 30 % (500 Ms) Conforming To IEC 61000-4-11
     • Immunity To Microbreaks And Voltage Drops - Test Level: 100 % (20 Ms) Conforming To IEC 61000-4-11
     • Minimum Pulse Duration : 100 Ms With Load In Parallel
     • 30 Ms
     • Maximum Switching Current : 8 A
     • Voltage Range : 0.85...1.1 Us
     • Maximum Switching Voltage : 250 V AC
     • Functionality : Multifunction
     • Temperature Drift : +/- 0.05 %/°C
     • Pollution Degree : 3 Conforming To IEC 60664-1
     • Directives : 2004/108/Ec - Electromagnetic Compatibility
     • 2006/95/Ec - Low Voltage Directive
     • Ambient Air Temperature For Storage : -40-70 °C
     • Minimum Switching Current : 10 Ma At 5 V DC
     • Relative Humidity : 95-95 % At 25-55 °C
     • Electrical Durability : 100000 Cycles, 8 A At 250 V, Ac-1
     • 100000 Cycles, 2 A At 24 V, Dc-1
     • Mechanical Durability : 10000000 Cycles
     • IP Degree Of Protection : Ip40 Housing: Conforming To IEC 60529
     • IP20 Terminals: Conforming To IEC 60529
     • Ip50 Front Panel: Conforming To IEC 60529
     • [Uimp] Rated Impulse Withstand Voltage : 5 Kv For 1.2-50 µs Conforming To IEC 60664-1
     • Tightening Torque : 0.6-1 N.M Conforming To IEC 60947-1
     • [Uc] Control Circuit Voltage : 24...240 V
     • Device Short Name : Re22

    Minimum sell quantity:

    Order Quantity Multiple:

    Catalogue Page Number: 17-70

    Technical Specifications

    Contact Type 2 C/O
    1 C/O Timed Or Instantaneous Contact, Cadmium Free
    2 C/O Timed Contact, Cadmium Free
    2 C/O
    Voltage Rating 24...240 V Ac/Dc 50/60 Hz
    Height 26 mm
    Width 22.5 mm
    Weight 0.105 Kg
    Length 95 mm