Skip to content Skip to navigation menu
click to open Expanded view

Terasaki - T2 MCCB 36Ka 4P 250A - S250NJ4250

  • TERASAKI
  • BW#: 00813879
  • Mfr#: S250NJ4250
  • UNSPSC#: 39121616
Login or Register to view price
QTY



Specifications

 • Service Information: Product is not repairable
 • Product Series: TemBreak 2 MCCB
 • Standards Compliance: IEC 60947-2, EN 60947-2, JIS C 8201-2-1 Ann.1, AS/NZS 60947-2, NEMA AB1
 • Certifications: CE, ASTA
 • Shipping Approvals: Contact NHP
 • Component Type MCCB: MCCB AC
 • Standard Installation Method: Front Connection
 • Trip Unit Protection Type: Adjustable Thermal Adjustable Magnetic
 • Im, Magnetic Trip Current, Max: 2000 A
 • Im, Magnetic Trip Current, Min: 1500 A
 • In, Rated Current at 45°C: 250 A @45°C
 • Ics, Rated Service Short-Circuit Breaking Capacity, 440V AC: 25 kA
 • Ics, Rated Service Short-Circuit Breaking Capacity, 525V AC: 18 kA
 • Ics, Rated Service Short-Circuit Breaking Capacity, 690V AC: 7.5 kA @690VAC
 • Ics, Rated Service Short-Circuit Breaking Capacity, AC (IEC 60947): 100 % Icu
 • Ir, Thermal Trip Current, Max: 250 A
 • Ir, Thermal Trip Current, Min: 160 A
 • Icu, Rated Ultimate Short-Circuit Breaking Capacity, 240V AC: 65 kA @240VAC
 • Icu, Rated Ultimate Short-Circuit Breaking Capacity, 400/415V AC: 36 kA @400/415VAC
 • Icu, Rated Ultimate Short-Circuit Breaking Capacity, 440V AC: 25 kA @440VAC
 • Icu, Rated Ultimate Short-Circuit Breaking Capacity, 525V AC: 25 kA @525VAC
 • Icu, Rated Ultimate Short-Circuit Breaking Capacity, 690V AC: 7.5 kA @690VAC
 • Icu, Rated Ultimate Short-Circuit Breaking Capacity, 250V DC: 40 kA @250VDC
 • Depth: 68 mm
 • Frame Size: 250 AF size
 • Rated Frequency: 50/60 Hz
 • Height: 165 mm
 • Number of Poles: 4
 • Poles: 4P
 • Electrical Service Life at Un, In: 10000 cycles
 • Mechanical Service Life: 30000 cycles
 • Magnetic Trip Type: Adjustable type
 • Thermal Trip Type: Adjustable type
 • Uimp, Impulse Withstand Voltage: 8 kV
 • Ui, Rated Insulation Voltage: 800 V (rms)
 • Ue, Rated Operational Voltage, AC, max: 690 V AC
 • Ue, Rated Operational Voltage, DC, max: 250 V DC
 • Weight: 1.9 kg
 • Width: 140 mm
 • Reverse Connection Of Supply Possible: Yes

Minimum sell quantity:

Order Quantity Multiple:

Technical Specifications

Type MCCB AC
Number of Pole 4
Height 165 mm
Width 140 mm
Weight 1.9 kg
Rated Current 250 A @45°C
Rated Insulation Voltage 800 V (rms)
Trip Unit Technology Adjustable Thermal Adjustable Magnetic
Customers Also Bought