Features
  • Protection: when detecting significant leakage current in the line it monitors, the relay trips the breaker at the top end of it, through its shunt trip auxiliary
  • Monitoring: signalling leakage current by LED, bargraph or digital display on front, and by an output dry contact. Available in single-line and multi-line variants monitoring up to 12 different distribution lines.
  • Residual current sensitivity ranging from 30 mA to 30 A, fixed or adjustable, for A type relays,
    and 30 mA to 3 A for B type relays
  • Trip time delay ranging from 0 to 4.5 seconds, fixed or adjustable
    o Networks with operating voltage up to 1000 V, and frequency up to 400 Hz
    o lines with current carrying capacity up to 3200 A
    o main switchboards (at the foot of the transformer) in most demanding industrial environments (overvoltage withstand category IV)
  • Type A or type B as per IEC 60 755
  • Compliant with standards:
    o IEC 60 755 and IEC 60947-2 appendix M (certificates by Kema laboratories available)
    o UL 1053 listed, CSA C22.2 N° 144 for North-America
    o EAC for Russia, CCC for China
  • DIN profile, to clip on rail or secure on backplate
  • 72x72mm, for switchboard front plate or door mounting, using clips
    o Closed toroids; for new installations (new switchboards or extensions), with cable capacity up to 630 A for A type relays, 250 A for B type relays
    o Rectangular sensors; for lines with capacity up to 3200 A (busbars, or cables above 630 A)
    o Split toroids; to equip distribution lines already in operation, with cable capacity up to 250 A


  • Applications
  • Electrical networks operating with voltage above 500 V (up to 1000) or frequency higher than 60 Hz (up to 400)
  • Distribution lines with capacity 630 A and above (up to 3200)
  • Upgrade of switchboards already in operation
  • Monitoring and protection at the root of power distribution
  • Three-phase supplied loads including rectifiers : lifts, cranes, HVAC, high-power speed drives, UPS...
  • Single-phase DC boost power supply in some electric vehicle chargers
  • Loads including single-phase speed drives: washing machines, air-conditioning units, heat pumps, food processors)
  • power supply network equipped with harmonic filters


  • Specifications

    • Range of product:Vigirex

    • Device short name:RH99M

    • Product or component type:Residual current protection relay

    • Range compatibility:Vigirex RH TOA earth leakage current sensor

    • Vigirex RH A earth leakage current sensor

    • Relay application:Residual current protection relay

    • Earthing system:TN-S,IT,TT

    • [Us] rated supply voltage:12...24 V AC 50/60 Hz 12...48 V DC

    • Power consumption in VA:4 VA

    • Type of measurement:Earth fault current internal measurement, range: 80...100 %

    • Residual earth-leakage time delay adjustment type:Instantaneous 0.03 A

    • Adjustable 9 settings 0.03…30 A 0…4.5 s

    • Test function:Remote test Local

    • Monitoring:Electronics (continuous)

    • Power supply (continuous)

    • Relay/sensor link (continuous)

    • [The] conventional enclosed thermal current:8 A

    • Minimum load:10 mA at 12 V

    • Net weight:0.3 kg

    • Mechanical robustness :Fire resistance conforming to IEC 60695-2-1 IK protection 2 joules: IK07 conforming to EN 50102 IP protection: IP20 conforming to IEC 60529 IP protection: IP30 conforming to IEC 60529 IP protection: IP40 conforming to IEC 60529 Vibrations 13.2...100 Hz: 0.7 g Vibrations 2...13.2 Hz: +/- 1 mmEarth-leakage protection class:Class AC,Class A si

    • Overvoltage category:IV

    • Tamperproof of settings:Protected by sealable cover

    • Mounting support:DIN rail

    • Height:97 mm

    • Width:54 mm

    • Depth:74 mm

    • 9 mm pitches:6

    • Connections - terminals:Auxiliary power supply: terminal block cable(s) 0.2…2.5 mm² flexible AWG 24...AWG 12

    • Auxiliary power supply: terminal block cable(s) 0.2…2.5 mm² rigid AWG 24...AWG 12

    • Auxiliary power supply: terminal block cable(s) 0.25…2.5 mm² flexible AWG 24...AWG 12

    • Fault: screw terminal cable(s) 0.2…2.5 mm² flexible AWG 24...AWG 12

    • Fault: screw terminal cable(s) 0.2…4 mm² rigid AWG 24...AWG 12

    • Fault: screw terminal cable(s) 0.25…2.5 mm² flexible AWG 24...AWG 12

    • Relay test and fault reset: screw terminal cable(s) 0.14…1 mm² flexible AWG 26...AWG 16

    • Relay test and fault reset: screw terminal cable(s) 0.14…1.5 mm² rigid AWG 26...AWG 16

    • Relay test and fault reset: screw terminal cable(s) 0.25…0.5 mm² flexible AWG 26...AWG 16 Sensor: screw terminal cable(s) 0.14…1 mm² flexible AWG 26...AWG 16 Sensor: screw terminal cable(s) 0.14…1.5 mm² rigid AWG 26...AWG 16

    • Sensor: screw terminal cable(s) 0.25…0.5 mm² flexible AWG 26...AWG 16

    • Voltage presence: screw terminal cable(s) 0.2…2.5 mm² flexible AWG 24...AWG 12

    • Voltage presence: screw terminal cable(s) 0.2…4 mm² rigid AWG 24...AWG 12

    • Voltage presence: screw terminal cable(s) 0.25…2.5 mm² flexible AWG 24...AWG 12

    • Wire stripping length:Auxiliary power supply: 7 mm for top connection Fault: 8 mm for bottom connection Relay test and fault reset: 5 mm for bottom connection Sensor: 5 mm for top connection Voltage presence: 8 mm for bottom connection

    • Tightening torque:Auxiliary power supply: 0.6 N.m top Fault: 0.6 N.m bottom

    • Relay test and fault reset: 0.25 N.m bottom Sensor: 0.25 N.m top

    • Voltage presence: 0.6 N.m bottom

    Minimum sell quantity:

    Order Quantity Multiple:

    Technical Specifications

    Type Residual current protection relay
    Mounting Type DIN rail
    Height 85 mm
    Width 54 mm
    Weight 0.3 kg
    Length 76 mm
    Air temperature for operation -35…70 °C
    Air temperature for storage -55…85 °C