Features
  • DIN rail mounting Free tripping mechanism even if toggle is locked or sealed ON or OFF


Specifications

 • Standards compliance : AS/NZS 61008 EN 61008-1 IEC 61008-1
 • Certifications : CE RCM
 • Add-on devices (side add-on) : Auxiliary contacts PBS Tele L Tele M Tele U
 • Component type power distribution & protection : RCD
 • Number of poles versus modules : 4
 • Tripping time at I?n, Instantaneous : 40
 • Tripping time at I?n, Selective : >150
 • Approval(s) : N17482
 • Busbar system, bottom : Fork pin
 • Busbar system, top : Fork pin
 • Selectivity class (IEC 60898) : A
 • I?n, rated leakage current : 30
 • Im, Rated make/break capacity : 500
 • I?m, rated residual make/break capacity : 500
 • In, rated current at 30°C : 63
 • Inc, rated conditional short circuit current : 10
 • I?c, rated conditional residual short-circuit current : 10000
 • Depth : 76
 • Dielectric strength : 2500V
 • Grid distance (safety difference between 2 devices) : 35

Minimum sell quantity:

Order Quantity Multiple:

Technical Specifications

Type RCD
Number of Pole 3P + N
Voltage Rating 415 V AC
Current Rating 63 A @30°C
Depth 76 mm
Width 72 mm
Height 86 mm
Colour White
Weight 0.368 kg
Mounting Mode DIN-35 Rail Mount
Rated Impulse Withstand Volt 6 kV
Rated Insulation Voltage Ui, Rated Insulation Voltage @ Pollution Degree 2 - 440 V
Standards Compliance AS/NZS 61008, EN 61008-1, IEC 61008-1