Specifications

  • Standards Compliance: IEC 61000-4-2 IEC 61000-4-3 IEC 61000-4-4 IEC 61000-4-5 IEC 61000-4-6 GB 14048-11 IEC 60947-6-1 IEC 60947-3
  • Certifications: CE RoHS
  • Component Type Power Distribution & Protection: Automatic Transfer Switch
  • Altitude, Operating (No Derating): 2000
  • Ie, Rated Operational Current, DC-20a, 220V: 160
  • Ie, Rated Operational Current, DC-20b, 220V: 160
  • Ie, Rated Operational Current, DC-21a, 220V: 160
  • Ie, Rated Operational Current, DC-21b, 220V: 160
  • Ie, Rated Operational Current, DC-22a, 220V: 160
  • Ie, Rated Operational Current, DC-22b, 220V: 160
  • Ie, Rated Operational Current, DC-23a, 220V: 125
  • Ie, Rated Operational Current, DC-23b, 220V: 125
  • Ie, Rated Operational Current, AC-21a, 415V: 160
  • Ie, Rated Operational Current, AC-21b, 415V: 160
  • Ie, Rated Operational Current, AC-22a, 415V: 160
  • Ie, Rated Operational Current, AC-22b, 415V: 160
  • Ie, Rated Operational Current, AC-23a, 415V: 160
  • Ie, Rated Operational Current, AC-23b, 415V: 160
  • Ie, Rated Operational Current, AC-31b, 415V: 160
  • Ie, Rated Operational Current, DC-20a, 440V: 160
  • Ie, Rated Operational Current, DC-20b, 440V: 160
  • Ie, Rated Operational Current, DC-21a, 440V: 125
  • Ie, Rated Operational Current, DC-21b, 440V: 125
  • Ie, Rated Operational Current, DC-22a, 440V: 125
  • Ie, Rated Operational Current, DC-22b, 440V: 125
  • Ie, Rated Operational Current, DC-23a, 440V: 125
  • Ie, Rated Operational Current, DC-23b, 440V: 125
  • Ie, Rated Operational Current, AC-21a, 690V: 160
  • Ie, Rated Operational Current, AC-21b, 690V: 160
  • Ie, Rated Operational Current, AC-22a, 690V: 125
  • Ie, Rated Operational Current, AC-22b, 690V: 125
  • Ie, Rated Operational Current, AC-23a, 690V: 63
  • Ie, Rated Operational Current, AC-23b, 690V: 80
  • Current, Fuse-Protected Short-Circuit Capacity, 400V: 100
  • Icw, short time withstand current, 1s (rms): 7
  • Ipk, Peak Current, Max: 20000
  • Ith, Thermal Current at 40°C: 160
  • Depth: 244
  • Details, Thermal Current: Derating correction factor(Kt) applys from 40°C to 70°C
  • Kt=0.9 for temperature from 40°C to 50°C; Kt=0.8 for temperature from 50°C to 60°C; Kt=0.7 for temperature from 60°C to 70°C
  • Frame Size: B3
  • Fuse Current Rating: 160
  • Height: 154
  • Relative Humidity, Max: 95
  • Humidity type: Non-condensing
  • Number of Poles: 3
  • Mechanical service life: 10000
  • Operating Temperature, Max: 40
  • Operating Temperature, Min: -20
  • Storage Temperature, Max: 70
  • Storage Temperature, Min: -40
  • Electrical Blackout Time (I - II): 0.3
  • Switching Time (I - 0/II - 0): 0.45
  • Switching Time (I - II/II - I): 0.75
  • Supply Power, Inrush: 184
  • Supply Power, Rated, AC 50Hz: 92
  • Uimp, Impulse Withstand Voltage: 8
  • Ui, Rated Insulation Voltage: 800
  • Umax, Supply Voltage, AC, Max: 332
  • Umin, Supply Voltage, AC, Min: 166
  • Unom, Supply Voltage, AC, Nom: 250
  • Weight: 5.7
  • Width: 304
  • Busbar Width, Max: 25
  • Cable Cross Section (Max): 95 mm²
  • Cable Cross Section (Min): 50 mm²
  • Minimum sell quantity:

    Order Quantity Multiple:

    Technical Specifications

    Type Automatic Transfer Switch
    Pole 3
    Height 370 mm
    Width 360 mm
    Length 480 mm
    Weight 5700 g
    Mechanical Durability 10000 cycles