Skip to content Skip to navigation menu
click to open Expanded view

Socomec - Load Break Switch Slbm 3P 125A External Handle Kit - SLBM1253P

  • socomec
  • BW#: 00866341
  • Mfr#: SLBM1253P
  • UNSPSC#: 32101522
Login or Register to view price
QTY

Features
  • Double break per pole offers high durability and short-circuit withstand


  • Specifications

  • Service Information: Product is not repairable
  • Product Series: SLB
  • Im, Rated Make/Break Capacity, 4-Pole, DC-21b, 400V: 63 A 4P@400V
  • Ie, Rated Operational Current, DC-20a, 110V: 125 A@110V
  • Ie, Rated Operational Current, DC-20b, 110V: 125 A@110V
  • Ie, Rated Operational Current, DC-21a, 110V: 125 A@110V
  • Ie, Rated Operational Current, DC-21b, 110V: 125 A@110V
  • Ie, Rated Operational Current, DC-20a, 250V: 125 A@250V
  • Ie, Rated Operational Current, DC-20b, 250V: 125 A@250V
  • Ie, Rated Operational Current, DC-21a, 250V: 125 A@250V
  • Ie, Rated Operational Current, DC-21b, 250V: 125 A@250V
  • Ie, Rated Operational Current, AC-21a, 400V: 125 A@400V
  • Ie, Rated Operational Current, AC-22a, 400V: 125 A@400V
  • Ie, Rated Operational Current, AC-23a, 400V: 125 A@400V
  • Ie, Rated Operational Current, DC-20a, 400V: 125 A@400V
  • Ie, Rated Operational Current, DC-20b, 400V: 125 A@400V
  • Ie, Rated Operational Current, DC-21a, 400V: 63 A@400V
  • Ie, Rated Operational Current, AC-20a, 415V: 125 A@415V
  • Ie, Rated Operational Current, AC-20b, 415V: 125 A@415V
  • Ie, Rated Operational Current, AC-21a, 415V: 125 A@415V
  • Ie, Rated Operational Current, AC-21b, 415V: 125 A@415V
  • Ie, Rated Operational Current, AC-22a, 415V: 125 A@415V
  • Ie, Rated Operational Current, AC-22b, 415V: 125 A@415V
  • Ie, Rated Operational Current, AC-23a, 415V: 125 A@415V
  • Ie, Rated Operational Current, AC-23b, 415V: 125 A@415V
  • Ie, Rated Operational Current, AC-20a, 500V: 125 A@500V
  • Ie, Rated Operational Current, AC-20b, 500V: 125 A@500V
  • Ie, Rated Operational Current, AC-21a, 500V: 125 A@500V
  • Ie, Rated Operational Current, AC-21b, 500V: 125 A@500V
  • Ie, Rated Operational Current, AC-22a, 500V: 125 A@500V
  • Ie, Rated Operational Current, AC-22b, 500V: 125 A@500V
  • Ie, Rated Operational Current, AC-23a, 500V: 100 A@500V
  • Ie, Rated Operational Current, AC-23b, 500V: 100 A@500V
  • Ie, Rated Operational Current, AC-20a, 690V: 125 A@690V
  • Ie, Rated Operational Current, AC-20b, 690V: 125 A@690V
  • Ie, Rated Operational Current, AC-21a, 690V: 125 A@690V
  • Ie, Rated Operational Current, AC-21b, 690V: 125 A@690V
  • Ie, Rated Operational Current, AC-22a, 690V: 100 A@690V
  • Ie, Rated Operational Current, AC-22b, 690V: 125 A@690V
  • Ie, Rated Operational Current, AC-23a, 690V: 63 A@690V
  • Ie, Rated Operational Current, AC-23b, 690V: 63 A@690V
  • In, Rated Current: 125 A
  • Icw, Short Time Withstand Current, 300ms (rms): 5 kA, 300ms
  • Ith, Thermal Current at 40°C: 125 A
  • Height: 131.4 mm
  • kW Rating, AC-23a, 415V, 3ph: 55 kW @415V
  • Number of Poles: 3
  • Mechanical Service Life: 100000 cycles
  • Uimp, Impulse Withstand Voltage: 8 kV
  • Ui, Rated Insulation Voltage: 800 V (rms)
  • Weight: 0.7 kg
  • Width: 78 mm
  • Cable Cross Section (Max): 70 mm²
  • Cable Cross Section (Min): 10 mm²
  • Minimum sell quantity:

    Order Quantity Multiple:

    Technical Specifications

    Current Rating 125 A
    Pole 3
    Height 85 mm
    Width 320 mm
    Length 95 mm
    Weight 800 g
    Mechanical Durability 100000 cycles