Skip to content Skip to navigation menu
click to open Expanded view
Schneider Electric Schneider Electric (View All Products)

Schneider Electric A9MEM1580 PowerLogica - PowerTag Energy Sensor Flex 160A 3P/3P+N Top And Bottom Position

  • Schneider Electric
  • BW#: 03364644
  • Mfr#: A9MEM1580
  • UNSPSC#: 32101522
Login or Register to view price
QTY

Features
  • Accurate real-time measurements and energy values
  • Pre-alarm notification in the event of overcurrent
  • Real-time alarm and email notification for voltage loss, overload trip
  • PowerTag Energy contributes to your energy efficiency and carbon footprint reduction targets
  • It supports Energy Efficiency programs (EED, EPBD) and standards (IEC 60364-8-1, EN 17267, ISO 50001)


  • Specifications

     • [Ib] Basic Current : 25 A
     • [Ue] Rated Operational Voltage : 100...277 V Ac, 173...480 V Ac
     • Accuracy Class : Class 1 Active Energy Conforming To Iec 61557-12, Class 2 Reactive Energy Conforming To Iec 61557-12, Class 2 Apparent Energy Conforming To Iec 61557-12, Class 1 Active Power Conforming To Iec 61557-12, Class 2 Reactive Power Conforming To Iec 61557-12, Class 2 Apparent Power Conforming To Iec 61557-12, Class 1 Current Conforming To Iec 61557-12, Class 0.5 Voltage Conforming To Iec 61557-12, Class 1 Power Factor Conforming To Iec 61557-12, Class 0.5 Frequency Conforming To Iec 61557-12
     • Cable Cross Section : 1 Rigid Cable 0.2-1.5 Mm² Without Cable End, 1 Stranded Cable 0.2-2.5 Mm² Without Cable End, 1 Stranded Cable 0.25-1.5 Mm² With Cable End
     • Colour : White (Ral 9003)
     • Concentrator Compatibility : Acti9 Powertag Link C, Acti9 Powertag Link, Acti9 Powertag Link Hd, Harmony Hub, Ecostruxure Panel Server Universal, Ecostruxure Panel Server Advanced, Prismaset Active
     • Connection Pitch : 27 Mm
     • Depth : 62 Mm
     • Directives : 2014/53/Eu - Radio Equipment Directive
     • Electrical Connection : Removable Spring Terminal Block
     • Electromagnetic Compatibility : Industrial Electromagnetic Environment Conforming To Iec 61326-1, Radiated Emc Conforming To Etsi En 301 489-17, Electromagnetic Emission Conforming To Iec 62311
     • Emission Power : 10 Mw
     • Environmental Characteristic : Indoor Use
     • Event Management : Voltage Loss With Measured Current At Voltage Loss
     • Form Factor : Flex
     • Ik Degree Of Protection : Ik05
     • Ip Degree Of Protection : Ip20 Conforming To Iec 60529
     • Max Current : 160 A
     • Maximum Cable Outer Diameter : 17 Mm
     • Measurement Category : Category Iv Conforming To Iec 61010-2-030
     • Metering Type : Active Energy E -A- In/Out 0...281 X 10Exp(9) Kwh At Total Per Phase, Active Energy E -A- In/Out 0...281 X 10Exp(9) Kwh At Partial Per Phase, Active Energy E -A- In/Out 0...281 X 10Exp(9) Kwh At 3-Phase Total, Active Energy E -A- In/Out 0...281 X 10Exp(9) Kwh At 3-Phase Partial, Reactive Energy E -Ra- In/Out 0...281 X 10Exp(9) Kvarh At Total Per Phase, Reactive Energy E -Ra- In/Out 0...281 X 10Exp(9) Kvarh At Partial Per Phase, Reactive Energy E -Ra- In/Out 0...281 X 10Exp(9) Kvarh At 3-Phase Total, Reactive Energy E -Ra- In/Out 0...281 X 10Exp(9) Kvarh At 3-Phase Partial, Apparent Energy E -Apa- 0...281 X 10Exp(9) Kvah At Total Per Phase, Apparent Energy E -Apa- 0...281 X 10Exp(9) Kvah At Partial Per Phase, Apparent Energy E -Apa- 0...281 X 10Exp(9) Kvah At 3-Phase Total, Apparent Energy E -Apa- 0...281 X 10Exp(9) Kvah At 3-Phase Partial, Active Power P, Reactive Power Q, Apparent Power S, Current I1, Calculated Neutral Current, Voltage U12, Voltage V1N, Frequency 45...65 Hz, Power Factor At Per Phase, Power Factor At Total
     • Mounting Location : Top Or Bottom
     • Mounting Mode : Free Mounting
     • Mounting Support : Cables
     • Network Frequency : 50 Hz, 60 Hz
     • Operating Altitude : 0...2000 M
     • Overvoltage Category : Iv Conforming To Iec 61010-1
     • Poles Description : 3P, 3P + N
     • Pollution Degree : 3
     • Power Consumption In Va : 3 Va
     • Product Destination : Switchboard
     • Product Name : Powertag F160
     • Product Specific Application : Energy Management, Overload Alarm, Power Factor, Load Monitoring, Circuit Monitoring
     • Quality Labels : Ce
     • Range : Powerlogic
     • Range Compatibility : Acti 9 C120, Acti9 Ng125, Compact Nsxm, Tesys Gv4, Compact Ins, Acti9 Isw, Acti9 Isw-Na, Acti9 Iid, Powerpact B
     • Relative Humidity : 0-95 % At 55-55 °C Conforming To Iec 60721-3-3
     • Saturation Current : 320 A
     • Standards : Iec 61557-12, Iec 61010-1, Etsi En 301 487-1, Iec 61010-2-030, Iec 61326-1, Etsi En 300 328
     • Starting Current : 100 Ma
     • Transmission Support Medium : Radio Frequency 2.4-2.4835 Ghz Conforming To Ieee 802.15.4
     • Type Of Measurement : Active And Reactive Energy, Apparent Energy, Active And Reactive Power, Apparent Power, Current, Voltage, Power Factor, Internal Temperature, Frequency
     • Vibration Resistance : 3M4 Conforming To Iec 60721-3-3
     • Width : 91 Mm
     • Wire Stripping Length : 11 Mm

    Minimum sell quantity:

    Order Quantity Multiple:

    Technical Specifications

    Type Energy sensor
    Height 39 mm
    Weight 80 g
    Air Temperature for Storage -50-85 °C
    Air Temperature for Operation 25-70 °C
    Customers Also Bought