Skip to content Skip to navigation menu
click to open Expanded view
Schneider Electric Schneider Electric (View All Products)

Schneider Electric TeSys GV4 GV4L02N Motor Circuit Breaker - Magnetic Everlink Terminals - 3P - 2A Icu - 50kA

  • Schneider Electric
  • BW#: 00470785
  • Mfr#: GV4L02N
  • UNSPSC#: 39122000

Features
  • GV4 Type L: Magnetic short circuit protection to be used with an overload relay or a drive
  • GV4 Type P : Magnetic short circuit and overload protection
  • GV4 PEM: Magnetic short circuit and overload protection with advanced settings and pre-alarming
  • Covers motor protection from 0.25 to 55 kW at 415 V AC (from 0.8 to 115 A) all in one frame
  • Available in three different breaking capacities: 25, 50 and 100 kA at 415 V AC IEC (15, 35, 65 kA at 480 V UL)
  • Patented EverLink creep-compensating technology: Spring-based system ensures a long-lasting connection, improve overheating leading to trip, reduce risk during short circuit
  • Ergonomic rotary handle for easy switching and controlling with clear trip indication
  • Other options include: Toggle, side, extended


  • Applications
  • Oil & Gas
  • Wastewater treatment facilities
  • Mining
  • Energy


  • Specifications

    • [In] Rated current: 2 A

    • Breaking capacity: [Icu] : 50 kA at 380 415 V AC 50/60 Hz according to IEC 60947-2

    • Range: TeSys

    • [Ics] Rated service breaking capacity: 50 kA : at 440 V AC 50/60 Hz according to IEC 60947-2

    • Device short name: GV4L

    • Trip unit rating: 12 28 A

    • [Ics] Rated service breaking capacity: 2 kA : at 660 690 V AC 50/60 Hz according to IEC 60947-2

    • Breaking capacity: [Icu] : 100 kA at 220 240 V AC 50/60 Hz according to IEC 60947-2

    • Breaking capacity: [Icu] : 15 kA at 525 V AC 50/60 Hz according to IEC 60947-2

    • Product or component type: Circuit breaker

    • Protection type: Short-circuit

    • Trip unit technology: Magnetic

    • Utilisation category: Category A

    • Device application: Motor

    • [Ics] Rated service breaking capacity: 25 kA : at 500 V AC 50/60 Hz according to IEC 60947-2

    • Breaking capacity: [Icu] : 8 kA at 660 690 V AC 50/60 Hz according to IEC 60947-2

    • Control type: Rotary handle

    • Poles description: 3P

    • [Ics] Rated service breaking capacity: 100 kA : at 220 240 V AC 50/60 Hz according to IEC 60947-2

    • [Ics] Rated service breaking capacity: 50 kA : at 380 415 V AC 50/60 Hz according to IEC 60947-2

    • [Ics] Rated service breaking capacity: 15 kA : at 525 V AC 50/60 Hz according to IEC 60947-2

    Minimum sell quantity:

    Order Quantity Multiple:

    Technical Specifications

    Type Circuit Breaker
    Height 132 mm
    Width 55 mm
    Weight 0.96 kg
    Length 155 mm
    Air temperature for operation -25-70 °C
    Pollution Degree 3
    Air temperature for storage -40-80 °C
    Product Certifications IEC
    CCC
    EAC
    EU-RO MR
    IP degree of protection IP40 conforming to IEC 60529
    Rated Supply Voltage 380...480 V
    380...480 V - 15...10 %
    Operating Position Any Position