Skip to content Skip to navigation menu
click to open Expanded view
Schneider Electric Schneider Electric (View All Products)

Schneider Electric TeSys GV3 GV3L25 Motor Circuit Breaker - Magnetic Rotary Handle EverLink Terminals - 3P - 25A

  • Schneider Electric
  • BW#: 00762471
  • Mfr#: GV3L25
  • UNSPSC#: 39122000

Features
  • Magnetic circuit breaker
  • Covers 25 to 80 A
  • 11 to 45 kW motor with 50 to 100 kA/400 V breaking capacity
  • Three-position (Start/Stop/Tripped) rotary handle, front face padlocking and other accessories
  • Three-phase, 690 V rated operational voltage (Ue) maximum
  • Operating temperature from -20° C to +60° C open operation
  • IP20 level for finger safe protection
  • Trip test button on front face
  • Common add-on contact and trip blocks and accessories with GV2
  • Patented EverLink creep-compensating technology provides many benefits: Spring-based system ensures a long-lasting power connection, reduce overheating leading to trip and also risk during short circuit, ensure the correct torque tightening each time when you install the products


  • Applications
  • TeSys GV3 can be used for a range of applications across industry, infrastructure and buildings, including:
  • Motor control and protection, in accordance with standards IEC 947-2 and IEC 947-4-1


  • Specifications

  • Magnetic tripping current : 350 A
  • Product or component type : Circuit breaker
  • Trip unit technology : Magnetic
  • Network type : AC
  • [Ics] Rated service short - circuit breaking capacity : 100 % at 440 V AC 50/60 Hz
  • Range of product : TeSys GV3
  • Breaking capacity : 100 kA Icu at 230/240 V AC 50/60 Hz
  • Breaking capacity : 6 kA Icu at 690 V AC 50/60 Hz
  • Product name : TeSys GV3
  • [Ics] Rated service short - circuit breaking capacity : 50 % at 690 V AC 50/60 Hz
  • [Ics] Rated service short - circuit breaking capacity : 100 % at 230/240 V AC 50/60 Hz
  • [Ics] Rated service short - circuit breaking capacity : 100 % at 400/415 V AC 50/60 Hz
  • Range : TeSys
  • Breaking capacity : 50 kA Icu at 440 V AC 50/60 Hz
  • Breaking capacity : 100 kA Icu at 400/415 V AC 50/60 Hz
  • Network frequency : 50/60 Hz
  • Utilisation category : AC-3 conforming to IEC 60947-4-1
  • Utilisation category : Category A conforming to IEC 60947-2
  • Poles description : 3P
  • [Ics] Rated service short - circuit breaking capacity : 50 % at 500 V AC 50/60 Hz
  • Device short name : GV3L
  • Minimum sell quantity:

    Order Quantity Multiple:

    Technical Specifications

    Type Circuit Breaker
    Height 132 mm
    Width 55 mm
    Weight 0.96 kg
    Length 132 mm
    Air temperature for operation -20-60 °C
    Network Frequency 50/60 Hz
    Air temperature for storage -40-80 °C
    Product Certifications CCC
    EAC
    BV
    LROS (Lloyds register of shipping)
    DNV-GL
    ABS
    UL
    CSA
    UKCA
    IP degree of protection IP20 conforming to IEC 60529
    Operating Altitude 0...3000 m
    Operating Position Any Position