Skip to content Skip to navigation menu

Select Delivery Method

Please enter your delivery address to check availability.
Select delivery address
Please enter valid address
Add A Delivery Address* Please enter valid address
Can't find address?Try Address Form
e.g.
  1. Blackwoods - Level 4
  2. Level 4
  3. Unit 7
  4. Lot 684
  5. Shop 11
Address Line 1 * Please enter valid address
e.g.
  1. 39-43 High Street
  2. 26 Talavera Road
Address Line 2 Please enter valid address
Suburb * Please enter a valid suburb
Postcode
State
Switch to search address
Please note, your account has been configured incorrectly, restricting your access to the website. Please contact your administrator or customer support on 13 73 23 for assistance.
Loading...
Please select your click and collect pick up Branch to check availability.
Loading...
click to open Expanded view
Schneider Electric Schneider Electric (View All Products)

Schneider Electric Vigirex LV481004 Residual Current Monitoring Relay - Front Panel Mounting - RMH - 30mA To 30A - 220/240V AC - 50/60Hz

  • Schneider Electric
  • BW#: 01209741
  • Mfr#: LV481004
  • UNSPSC#: 39101600
Login or Register to view price
QTY

Features
  • Protection: when detecting significant leakage current in the line it monitors, the relay trips the breaker at the top end of it, through its shunt trip auxiliary
  • Monitoring: signalling leakage current by LED, bargraph or digital display on front, and by an output dry contact. Available in single-line and multi-line variants monitoring up to 12 different distribution lines.
  • Residual current sensitivity ranging from 30 mA to 30 A, fixed or adjustable, for A type relays,
    and 30 mA to 3 A for B type relays
  • Trip time delay ranging from 0 to 4.5 seconds, fixed or adjustable
    o Networks with operating voltage up to 1000 V, and frequency up to 400 Hz
    o lines with current carrying capacity up to 3200 A
    o main switchboards (at the foot of the transformer) in most demanding industrial environments (overvoltage withstand category IV)
  • Type A or type B as per IEC 60 755
  • Compliant with standards:
    o IEC 60 755 and IEC 60947-2 appendix M (certificates by Kema laboratories available)
    o UL 1053 listed, CSA C22.2 N° 144 for North-America
    o EAC for Russia, CCC for China
  • DIN profile, to clip on rail or secure on backplate
  • 72x72mm, for switchboard front plate or door mounting, using clips
    o Closed toroids; for new installations (new switchboards or extensions), with cable capacity up to 630 A for A type relays, 250 A for B type relays
    o Rectangular sensors; for lines with capacity up to 3200 A (busbars, or cables above 630 A)
    o Split toroids; to equip distribution lines already in operation, with cable capacity up to 250 A


  • Applications
  • Electrical networks operating with voltage above 500 V (up to 1000) or frequency higher than 60 Hz (up to 400)
  • Distribution lines with capacity 630 A and above (up to 3200)
  • Upgrade of switchboards already in operation
  • Monitoring and protection at the root of power distribution
  • Three-phase supplied loads including rectifiers : lifts, cranes, HVAC, high-power speed drives, UPS...
  • Single-phase DC boost power supply in some electric vehicle chargers
  • Loads including single-phase speed drives: washing machines, air-conditioning units, heat pumps, food processors)
  • power supply network equipped with harmonic filters


  • Specifications

     • Range compatibility: Vigirex Vigirex RMH L rectangular sensor
     • Device short name: RMH
     • Range: Vigirex
     • Range of product: Vigirex
     • Relay application: monitoring relay
     • Product or component type: monitoring relay
     • Range compatibility: Vigirex Vigirex RMH RM12T multiplexer
     • Range compatibility: Vigirex Vigirex RMH TOA earth leakage current sensor
     • Range compatibility: Vigirex Vigirex RMH A earth leakage current sensor
     • Ik Degree Of Protection : Ik07 Conforming To EN 50102
     • Type Of Setting : Keypad
     • Modbus Address
     • Mechanical Robustness : Fire ResistanCE Conforming To IEC 60695-2-1
     • Ik Protection 2 Joules: Ik07 Conforming To EN 50102
     • Vibrations 13.2...100 Hz: 0.7 G
     • Vibrations 2...13.2 Hz: +/- 1 mm
     • Earth Leakage Current : 0.03-1 A, Adjustable In Step Of 0.001 A
     • 1-30 A, Adjustable In Step Of 0.1 A
     • Height : 72 mm
     • Ambient Air Temperature For Operation : -25-55 °C
     • Mounting Support : Front Panel
     • Range Compatibility : Toa Earth Leakage Current Sensor
     • A Earth Leakage Current Sensor
     • L Earth Leakage Current Sensor
     • Rm12T Multiplexer
     • Type Of Measurement : Earth Fault Current Internal Measurement, Range: 20...200 %, Accuracy: +/- 20 %
     • Network Rated Voltage : 1000-1000 V - Ac At 50/60 Hz (Maximum)
     • 1000-1000 V - Ac At 400 Hz (Maximum)
     • Communication Service : Modbus Slave
     • [Ithe] Conventional Enclosed Thermal Current : 8 A
     • Earthing System : Tn-S
     • It
     • Tt
     • Relay Application : Monitoring Relay
     • Electromagnetic Compatibility : Conducted And Radiated Emissions: , B, Conforming To Cispr 11
     • Conducted Radio-Frequency Immunity Test: , 3, Conforming To IEC 61000-4-6
     • Electrostatic Discharge Immunity Test: , 4, Conforming To IEC 61000-4-2
     • High-Energy Conducted Susceptibility: , 4, Conforming To IEC 61000-4-5
     • Low-Energy Conducted Susceptibility: , 4, Conforming To IEC 61000-4-4
     • Radiated Susceptibility: , 3, Conforming To IEC 61000-4-3
     • Environmental Characteristic : Exposure To Damp Heat Not In ServiCE Conforming To IEC 60068-2-30
     • Exposure To Damp Heat In ServiCE Conforming To IEC 60068-2-56
     • Salt Mist Conforming To IEC 60068-2-52
     • Net Weight : 0.3 Kg
     • Tamperproof Of Settings : Protected By Access Code
     • Range : Vigipact
     • Wire Stripping Length : Alarm Circuit: 6 mm
     • Multiplexer Connection: 6 mm
     • Pre Alarm: 6 mm
     • Voltage Presence: 6 mm
     • Power Supply: 6 mm
     • Residual Earth-Leakage Time Delay Adjustment Type : Instantaneous For 0.03-0.03 A
     • Adjustable 0-4.5 S For 0.03-30 A Adjustable In Step Of 10 Ms
     • Connections - Terminals : Alarm Circuit: Terminal Block Cable(S) 0.2-2.5 mm² Flexible Awg 22...Awg 12
     • Alarm Circuit: Terminal Block Cable(S) 0.2-2.5 mm² Rigid Awg 22...Awg 12
     • Multiplexer Connection: Terminal Block Cable(S) 0.2-2.5 mm² Flexible Awg 22...Awg 12
     • Multiplexer Connection: Terminal Block Cable(S) 0.2-2.5 mm² Rigid Awg 22...Awg 12
     • Pre Alarm: Terminal Block Cable(S) 0.2-2.5 mm² Flexible Awg 22...Awg 12
     • Pre Alarm: Terminal Block Cable(S) 0.2-2.5 mm² Rigid Awg 22...Awg 12
     • Voltage Presence: Terminal Block Cable(S) 0.2-2.5 mm² Flexible Awg 22...Awg 12
     • Voltage Presence: Terminal Block Cable(S) 0.2-2.5 mm² Rigid Awg 22...Awg 12
     • Power Supply: Terminal Block Cable(S) 0.2-2.5 mm² Flexible Awg 22...Awg 12
     • Power Supply: Terminal Block Cable(S) 0.2-2.5 mm² Rigid Awg 22...Awg 12
     • Residual Earth-Leakage Sensitity Adjustment Type : Adjustable
     • Power Consumption In VA : 8 Va
     • [Us] Rated Supply Voltage : 220...240 V AC 50/60 Hz 70...110 %
     • Pollution Degree : 3 Conforming To IEC 60664-1
     • Cut-Out Dimensions : 68 X 68 mm
     • Ambient Air Temperature For Storage : -40-85 °C
     • Relative Humidity : 95-95 % At 55-55 °C
     • IP Degree Of Protection : Ip40 On Front Face: Conforming To EN/IEC60529
     • Ip30 On Side Parts: Conforming To EN/IEC60529
     • IP20 On Connection Terminals: Conforming To EN/IEC60529
     • Refresh Time : 0.5 S
     • Test Function : Local
     • Remote Test (Via Communication)
     • Electrical Shock Protection Class : Class Ii
     • [Uimp] Rated Impulse Withstand Voltage : 8 Kv
     • Width : 72 mm
     • Overvoltage Category : Iv
     • Depth : 117 mm
     • Tightening Torque : Alarm Circuit: 0.5-0.5 N.M
     • Multiplexer Connection: 0.5-0.5 N.M
     • Pre Alarm: 0.5-0.5 N.M
     • Voltage Presence: 0.5-0.5 N.M
     • Power Supply: 0.5-0.5 N.M
     • Threshold Setting : 0.015...1 A Adjustable In Step Of 0.001 A Pre-Alarm
     • 1...30 A Adjustable In Step Of 0.1 A Pre-Alarm
     • 0.03...1 A Adjustable In Step Of 0.001 A Alarm
     • 1...30 A Adjustable In Step Of 0.1 A Alarm
     • Minimum Load : 10 Ma At 12 V
     • Signal Contacts Composition : 1 C/O Alarm Fail-Safe
     • 1 No Pre-Alarm Fail-Safe