Skip to content Skip to navigation menu

Select Delivery Method

Please enter your delivery address to check availability.
Select delivery address
Please enter valid address
Add A Delivery Address* Please enter valid address
Can't find address?Try Address Form
e.g.
  1. Blackwoods - Level 4
  2. Level 4
  3. Unit 7
  4. Lot 684
  5. Shop 11
Address Line 1 * Please enter valid address
e.g.
  1. 39-43 High Street
  2. 26 Talavera Road
Address Line 2 Please enter valid address
Suburb * Please enter a valid suburb
Postcode
State
Switch to search address
Please note, your account has been configured incorrectly, restricting your access to the website. Please contact your administrator or customer support on 13 73 23 for assistance.
Loading...
Please select your click and collect pick up Branch to check availability.
Loading...
click to open Expanded view

A.P.C.S. A.P.C.S - Transducer Current AC - 2000Vrms isolation - ACT241-1410

  • A.P.C.S.
  • BW#: 01113453
  • Mfr#: ACT241-1410
  • UNSPSC#: 39101600
Login or Register to view price
QTY

Features
  • Double surge protection is standard with all Series 200 loop powered transmitters to prevent failure due to spikes induced by DC switched inductive loads

  • Input output relation can be direct or reverse acting

  • Input output isolation up to 2kV is achieved through the use of an internal current

  • transformer

  • Base calibration is set with 2 metal film resistors and removable coding plugs on the main board

  • These links provide a convenient and user-friendly means of changing the input range in the field from 0 - 1 Amp to 0 - 5 Amps

  • Any other 2 ranges are available upon request

  • Final calibration is trimmed using the front accessible zero and span 15-turn trim adjustments

  • A front mounted LED and a test socket verifies module function and assist in calibration checks without disconnection of output wires


Applications
  • Used in load monitoring

  • The ACT241 is used in 12V battery systems


Specifications

  • Size: 23.5W x 71.5H x 109D (mm)

  • Mounting: Clip for 35mm DIN-Rail

  • Housing material: ABS

  • Connection: Screw terminals

  • Weight: 0.106 kg

  • AS-1384-1973: Class 0.2

  • Response time: < 500mS

  • Input range: 0.5A up to 10A

  • 1A or 5A standard, (50, 60 or 400Hz Sine)

  • Protection class: IP40 (IP65 use additional enclosure)

  • Calibration Accuracy: <0.2% from 10% up to 100% of range

  • Linearity: <0.2% from 10% up to 100% of range

  • Frequency dependence: <0.01%/Hz from 40 to 400Hz

  • Ambient operating range: -20...+70°C

  • Temperature drift error: <0.5% within operating range

  • Supply voltage: 7.5 - 40V continuous (50V 30 seconds)

  • Load change effect: < 0.1% up to RL max

  • Front zero adjust: + 20% / -10% typical

  • Front span adjust: ± 25% typical

  • Overload continuous: 150% of rated input

  • Short term (2 sec): 20 times rated input

  • Input/output isolation: 2kV rms continuous

  • Electromagnetic compatibility: Complies with AS/NZS 4251.1 (EN 50081.1)

  • The ACT241 accepts AC current from current transformer or direct load current ranging from 0.5A up to 10A

  • Standard output is 4 - 20mA with a minimum supply voltage of 7.5V

  • Other factory set output configurations are 10 - 50mA loop powered and 0 - 10mA, 0 -20mA or voltage output in 3-wire connection